The WALL IE by Helmholz is an industrial NAT Gateway/firewall that secures your automation network with secure communication and easy configuration.
Política de entrega (editar con el módulo de Información de seguridad y confianza para el cliente)
The Helmholz WALL IE 700-860-WAL01 is an industrial NAT gateway and firewall designed to integrate machines and automation cells into the production network in a controlled manner.
Its Basic NAT, NAPT, port forwarding and packet-filtering functions enable machines with existing IP configurations — including serial machines using identical IP addresses — to be connected without having to modify the complete internal network configuration.
The WALL IE separates the machine LAN from the production WAN and allows the user to define which communications may pass between the two networks.
| Specification | Description |
|---|---|
| Manufacturer | Helmholz |
| Model | WALL IE Standard |
| Article number | 700-860-WAL01 |
| Product type | Industrial NAT gateway and firewall |
| WAN interface | 1 × 10/100 Mbps Ethernet port |
| LAN interfaces | 3 × 10/100 Mbps Ethernet ports with integrated switch |
| Operating modes | NAT and Bridge |
| NAT functions | Basic NAT, SNAT, NAPT and port forwarding |
| IP filtering | IPv4 addresses, TCP/UDP protocols and ports |
| MAC filtering | Blacklisting and whitelisting |
| Traffic rules | Separate configuration for WAN-to-LAN and LAN-to-WAN traffic |
| DHCP | DHCP server on LAN and DHCP client on WAN |
| DNS | DNS server for the LAN network |
| Configuration | Responsive web interface; configuration import and export |
| Power supply | 24 VDC, 18–30 VDC operating range |
| Permissible ambient temperature | −40 to +75 °C |
| Protection rating | IP20 |
| Dimensions | 32.5 × 58.5 × 76.5 mm (depth × width × height) |
| Mounting | DIN rail |
| Certifications | CE and UL |
The WALL IE enables multiple machines manufactured with the same network structure and identical internal IP addresses to be integrated into the same production plant. Each machine is separated through NAT and can be represented on the production network using different external addresses.
This avoids individually reconfiguring the PLCs, HMIs, drives, cameras and other Ethernet devices installed inside each machine.
The separation between the LAN and WAN networks helps limit the traffic entering or leaving the machine. Packet filters can be used to permit only the addresses, protocols and ports required by the application.
Filtering broadcast and multicast traffic also helps reduce unnecessary network load on the production network.
Basic NAT: assigns a different external address to each internal device that must be accessible from the production network.
NAPT and port forwarding: provide access to several internal devices or services through one external IP address and different port numbers.
SNAT: facilitates communication with the machine network without changing the existing gateway or network configuration of certain devices.
Bridge mode: enables packet filtering when both sides belong to the same IP subnet and address translation is not required.
Before selecting the gateway, we recommend confirming:
Important: the standard WALL IE provides NAT, network segmentation and packet filtering. It does not incorporate UTM firewall functions such as deep packet inspection, antivirus, IDS/IPS or VPN. For applications requiring additional ports, Gigabit Ethernet or advanced management, the WALL IE Plus or another OT security solution should be considered.
At Garma Electrónica, we supply and configure Helmholz solutions for machine integration, industrial network segmentation and PROFINET communications.
Our technical team can help you define the NAT rules, external addresses, required ports and the most suitable WALL IE version for your network architecture.
Usually joint purchase